TPI 716A740 Combines: 716 Flue Gas Analyzer and A740 Infrared Printer - This is a state of the art, easy to use analyzer designed not only to display and calculate the required readings from a flue but also to cover most of the other measurements associated with combustion.
Using TPI analyzers to determine combustion
efficiency at the time of equipment set up minimizes call backs and can
be used to verify to the home owner the value of service work by showing
the increase in equipment efficiency after work is performed.
Efficiency calculation can also be used to generate business by
demonstrating the need to improve the efficiency of equipment or to show
the benefit of purchasing new equipment with higher efficiency.
- Built-in differential manometer with 0.001” H2O resolution
- Calculates combustion efficiency
- Data Logging with time and date stamp
- Will not shut off if 15 ppm CO is present for increased safety
- Communicate to a PC via the USB interface
- Optional A740 IR printer available for hard copies of test results
- Built-in differential thermometer
- Store function to save up to 10 readings
- Pump driven for fast response
- Push on fittings for fast and easy use
- Large easy to read backlit display
- Ten selectable fuels
Flue Temperature Probe
|
Construction
|
Pistol Grip with Stainless Steel Shaft
|
Hose Length
|
8.2’ (2500mm)
|
Insertion Length
|
7.9” (200mm)
|
'K' Type Thermocouple Accuracy
|
+/- 0.3% of fullscale, +/- 2°F (1°C)
|
Maximum Temperature
|
1472°F (800°C)
|
Gases
|
Range
|
Resolution
|
Accuracy
|
Oxygen
|
0-25%
|
0.1%
|
+/- 0.3%
|
Carbon Monoxide (low)
|
0-10,000 ppm
|
1 ppm
|
(<100ppm) +/- 5 ppm
(>=100ppm) +/- 5%
|
Carbon Monoxide (high)
|
0-100,000 ppm
|
0.001%
|
>10,000ppm: +/- 10%
|
Nitric Oxide *
|
0-5000ppm
|
1 ppm
|
+/- 5ppm (<100ppm)
+/- 5% (<1000ppm)
+/- 10% (>1000ppm)
|
Carbon Dioxide
|
0-25%
|
0.1%
|
Calculated
|
CO/CO2 Ratio
|
0-0.999
|
0.001
|
Calculated
|
Combustion Efficiency
|
0-100%
|
0.1%
|
Calculated
|
Gas Leak Sensor
|
100-10,000ppm (calibrated to methane)
|
* if fitted
Pressure Measurement
|
Selectable Ranges
|
mbar, psi, inH2O, mmH2O, kPa, hPa,
inHg, mmHg, mH2O
|
Range
|
- 100 mbar to + 100 mbar
-10 kPa to + 10 kPa
-40 inH2O to 40 inH2O
|
Resolution
|
0.001 mbar (0~9.999 mbar)
0.01 mbar (10.00~99.99 mbar)
|
Accuracy
|
< 5 mbar: +/- 0.05 mbar
> 5 mbar: +/- 1% of reading
|
+/- (0.3% of rdg + 2°F) or
+/- (0.3% of rdg + 1°C)
Temperature Measurement
|
Input Type
|
K-Type thermocouple
|
Range
|
-58°F to 2372°F (-50°C to 1300°C)*
|
Resolution
|
1°F (1°C)
|
Accuracy
|
|
Model 716 Specifications
|
Instrument
|
Operating Temperature Range
|
14°F to +122°F (-10°C to +50°C)
|
Battery / Batery Life
|
Rechargeable Ni-MH / > 6 Hours
|
Charger Input Voltage
|
115V or 230V : 50/60 Hz AC
|
Fuels
|
Natural Gas, LPG, Light Oil, Heavy
Oil, Bituminous Coal,
Anthracite
Coal, Coke, Butane, Wood, Bagasse
|
Pressure Ranges
|
mbar, psi, inH2O, mmH2O, kPa, hPa,
inHg, mmHg, mH2O
|
Display
|
Backlit Graphic LCD
|
Data Storage
|
100 sets of readings, multiple pages
|
Time and Date
|
24 Hour Real Time Clock
|
Dimensions
|
7.8” (200mm) x 3.5” (90mm) x 2.4” (60mm)
|
Weight
|
1.1lbs (500g)
|
Conforms to
|
EN50379
|
Warning: This product may expose you to chemicals including lead which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
|
|
|